D1700 Series Command Set

 

The DGH D1700 series products use a simple command and response protocol. A module must be interrogated by a host computer to obtain data. A module will never initiate a command sequence in order to prevent communications collisions.

A command is initiated with a command prompt, may be a dollar sign ($) or pound sign (#). Following the prompt a single address character must be transmitted. Each module on a communications bus must be setup with a unique address. The address is followed by a two character command. Every command is terminated with a carriage return.

The module response begins with a response prompt, which is an asterisk (*) followed by the necessary data. Every response is terminated with a carriage return. Linefeeds after the carriage return are user selectable. See the table below for typical commands and their respective response messages.

Command Definition Typical Command  Typical Response 
ACK - Acknowledge $1ACK *
CB - Clear Bit $1CB0C *
CP - Clear Position $1CP12 *
DI -  Digital Input $1DI *0007
DO -  Digital Output $1DO1234 *
RA - Read Assignments $1RA *0F0F
RAB - Read Assignment Bit $1RAB0E *O
RAP - Read Assignment Position $1RAP14 *I
RB - Read Bit $1RB0E *1
RD - Read Data $1RD *+99999.99
RE - Read Event Counter $1RE *0001107
RID - Read IDentification $1RID *BOILER
RIV - Read Initial Value $1RIV *0F0F
RP - Read Position $1RP14 *0
RS - Read Setup $1RS *31070002
RSU - Read Setup $1RSU *31070002
RWT - Read Watchdog Timer $1RWT *+00010.00
SB - Set Bit $1SB0C *
SP - Set Position $1SP12 *
WE - Write Enable $1WE *
     
Write Protected Commands    
AIB - Assign Input Bit $1AIB0E *
AIO - Assign Input/Output $1AIO0F0F *
AIP - Assign Input Position $1AIP14 *
AOB - Assign Output Bit $1AOB0E *
AOP - Assign Output Position $1AOP14 *
CE - Clear Events $1CE *
EC - Events Clear $1EC *0000100
ID - IDentification $1IDBOILER *
IV - Initial Value $1IV0F0F *
RR - Remote Reset $1RR *
SU - Setup  $1SU310701C2 *
WT - Watchdog Timer $1WT+00010.00 *
     
Continuous Input/Output Mode Commands    
CIA - Set Continuous Input Address $1CIA31 *
CMC - Continuous Mode Change $1CMC *
CMD - Continuous Mode Disable $1CMD *
CME - Continuous Mode Edge Triggered $1CME *
CMT - Continuous Mode Timer $1CMT *
CT - Continuous Time (Set Time) $1CT+00010.00 *
RCM - Read Continuous Mode $1RCM *D,T,E,C
RCT - Read Continuous Time Variable $1RCT *+00010.00
RIA - Read Continuous Input Address $1RIA *31

 