D1400
RTD Input Modules
|
|
|
|
|
The
D1400 ADC module converts RTD temperature sensor input signals to digital information,
linearizes the digital data, scales in either degrees C or F, and
communicates the values to a host computer or PLC. The data values are
transmitted in ASCII to a host computer via RS232 or RS485 .
The
D1400 series modules can also be mounted on a DIN-Rail using the MK-1
mounting kit. |
|
|
|
 |
Accuracy:
+/-0.3 deg C. |
 |
Resolution:
0.1 degree (C or F). |
 |
Common
mode rejection: 100db at 50/60 Hz. |
 |
User
selectable degrees C or F scaling. |
 |
Input
connections: 2,3, or 4 wire. |
 |
Excitation
current: 0.25mA. |
 |
Max
lead resistance: 50 ohms |
 |
Input
protection to 120Vac. |
 |
Automatic
linearization and lead compensation. |
 |
One
open collector digital output (or LO Alarm). |
 |
Ranges: |
 |
0.00385 = -200 to +850C |
 |
0.00392 = -200 to +600C |
 |
0.00388 = -100 to +125C |
|
|
|
|
|
|