D1300
Thermocouple Input Modules
|
|
|
|
|
The
D1300 ADC module converts thermocouple temperature sensor input signals to digital information, linearizes the digital
data, scales in either degrees C or F, and communicates the values to a host computer or
PLC. The data
values are transmitted in ASCII to a host computer via RS232 or
RS485
.
The
D1300 series modules can also be mounted on a DIN-Rail using the MK-1
mounting kit. |
 |
| Typical
RS-232 Thermocouple Module |
|
| |
| Specifications: |
|
 |
Types:
J, K, T, E, R, S, B, C |
 |
Accuracy (errors from all sources) from 0 to +40C ambient: +/-1deg C
max (J,K,T,E types). +/-2.5 deg C max for (R,S,B,C types). |
 |
Resolution:
1 degree (C or F). |
 |
Common
mode rejection: 100db at 50/60 Hz. |
 |
User
selectable degrees C or F scaling. |
 |
Lead
resistance effect: <20uV per 350 ohms. |
 |
Input
burnout protection to 250 VAC. |
 |
Input
impedance: 100 megohm min. |
 |
Automatic
cold junction compensation and linearization. |
 |
Three
open-collector digital outputs. |
 |
Two
digital inputs. |
 |
Open
thermocouple indication. |
 |
One
digital input/60 Hz events counter |
| |
Note:
D1300M series does not contain Events Counter. |
 |
Thermocouple
Measurement Ranges: |
|
|
J= -200 to +760
C |
B=
0 to +1820 C |
|
K= -150 to +1250
C |
S=
0 to +1750 C |
|
T= -200 to +400
C |
R=
0 to +1750 C |
|
E= -100 to +1000
C |
C=
0 to +2315 C |
|
|
|
|
|
|
|